TAAAC Conductor (Thermally Activated Aluminum Alloy Conductor) is an advanced aluminum alloy overhead conductor designed for high-temperature applications in power transmission lines. With its heat-resistant aluminum alloy composition, TAAAC Conductor provides low-sag performance, making it ideal for modern smart grid infrastructure. Compared to traditional conductors like ACSR and ACSS, TAAAC offers superior mechanical strength, corrosion resistance, and high conductivity for energy-efficient power transmission.TAAAC conductor is used in the transformation of old lines, urban network capacity transformation, substation, power plant construction and general lines.
TAAAC is a concentrically stranded conductor composed of thermal resistant aluminum alloy wires (TAL).
IEC 61089 Round Wire Concentric Lay Overhead Electrical Stranded Conductors
IEC 62004 Thermal -Resistant Aluminum Alloy Wires For Overhead Line Conductor
|
Cross Sectional area |
Na/Dia of wire |
Approximately |
DC conduvtor Resistance at 20℃,max |
Calcuated breaking load min |
Current Carrying capacity |
Standard Delivery lenght |
||
|
Overall diameter |
Net weight |
|||||||
|
mm² |
Pcs/mm |
mm |
Kg/km |
Ω/km |
kgf |
n |
A |
m |
|
150 |
19/3.20 |
16 |
419 |
0.1910 |
2270 |
22268 |
700 |
5000 |
|
200 |
19/3.70 |
18.5 |
560 |
0.1430 |
3030 |
29724 |
850 |
5000 |
|
240 |
19/4.00 |
20 |
655 |
0.1220 |
3490 |
34236 |
945 |
3000 |
|
300 |
37/3.20 |
22.4 |
821 |
0.0958 |
4430 |
43458 |
1090 |
3000 |
|
400 |
37/3.70 |
25.9 |
1097 |
0.0737 |
5890 |
57780 |
1325 |
2000 |
|
510 |
37/4.20 |
29.4 |
1414 |
0.0571 |
7460 |
73182 |
1565 |
2000 |
|
660 |
61/3.70 |
33.3 |
1812 |
0.0448 |
9720 |
95353 |
1840 |
1500 |
|
850 |
61/4.20 |
37.8 |
2335 |
0.0347 |
12300 |
120663 |
2175 |
1000 |
|
980 |
91/3.70 |
40.7 |
2716 |
0.0302 |
14500 |
142245 |
2380 |
1000 |
|
1030 |
91/3.80 |
41.8 |
2865 |
0.0286 |
15320 |
150289 |
2465 |
1000 |
|
1260 |
91/4.20 |
46.2 |
3501 |
0.0234 |
18350 |
180013 |
2800 |
500 |
|
Nominal Cross section area |
Structure [number x diameter of wire] |
Calculation area cross cestion |
Approx. Diameter of conductor |
Min.breaking strength |
DC Resistance of conductor at 20℃ |
Approx Mass of conductor |
Current Carrying capacity |
|
|
mm² |
n |
mm |
mm² |
mm |
kN |
Ω/km |
Kg/km |
A |
|
120 |
19 |
2.80 |
117.0 |
14.00 |
17.5 |
0.2493 |
320.1 |
566 |
|
150 |
19 |
3.15 |
148.1 |
15.75 |
22.2 |
0.1970 |
405.1 |
659 |
|
200 |
19 |
3.65 |
198.8 |
18.25 |
29.2 |
0.1467 |
543.9 |
798 |
|
240 |
19 |
4.00 |
238.8 |
20.00 |
34.2 |
0.1220 |
654.5 |
897 |
|
300 |
37 |
3.20 |
297.6 |
22.40 |
44.5 |
0.0986 |
816.0 |
1036 |
|
400 |
37 |
3.70 |
397.8 |
25.90 |
58.0 |
0.0737 |
1097.0 |
1258 |
|
510 |
37 |
4.20 |
512.6 |
29.40 |
73.3 |
0.0571 |
1413.0 |
1491 |
|
660 |
61 |
3.70 |
655.9 |
33.30 |
95.6 |
0.0448 |
1812.0 |
1753 |
|
850 |
61 |
4.20 |
845.1 |
37.80 |
120.9 |
0.0342 |
2334.0 |
2073 |
|
980 |
61 |
3.70 |
978.4 |
40.70 |
142.7 |
0.0302 |
2714.0 |
2272 |
|
1030 |
91 |
3.80 |
1032.1 |
41.80 |
150.5 |
0.0286 |
2864.0 |
2353 |
|
1260 |
91 |
4.20 |
1260.8 |
46.20 |
180.3 |
0.0234 |
3499.0 |
2672 |
|
1600 |
127 |
4.00 |
1595.9 |
52.00 |
228.5 |
0.0186 |
4440.0 |
3083 |
|
2020 |
127 |
4.50 |
2019.5 |
58.50 |
289.0 |
0.0147 |
5616.0 |
3540 |
|
2500 |
127 |
5.00 |
2493.7 |
65.00 |
357.0 |
0.0118 |
6937.0 |
3988 |