AAAC CONDUCTOR

AAAC / All Aluminum Alloy Conductor

Application
Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics.

AAAC conductors are extensively used for overhead distribution and transmission lines adjacent to ocean coastlines where there can be a problem of corrosion in the steel of an ACSR construction.

The aluminum alloy conductors are used in replace of single-layer ACSR conductors to reduce power loss in overhead distribution and transmission lines, when replacing the aluminum conductor steel reinforced, the AAAC can save 5-8% of the construction cost.

AAAC referred to have higher strength but lower conductivity than pure aluminum Being lighter, alloy conductors can sometimes be used to advantage in replace of the more conventional ACSR.

Standard

ASTM B399, BS EN50183, BS 3242, DIM 48201, IEC 61089

Features
Aluminum alloy conductors have a number of advantages over the use of the ACSR or AAC (all aluminum conductors). Lower power losses than for equivalent single aluminum-layer ACSR conductors. (The inductive effect of the steel core in the ACSR is eliminated).

Simpler fittings than those required for ACSR.

Excellent corrosion resistance in environments conducive to galvanic corrosion in ACSR.

Strength and sag approximately the same as for equivalent 6/1 and 26/7 ACSR conductors.

Outside diameters are the same as for standard ACSR conductors, permitting interchangeability of fittings.

Greater resistance to abrasion than that for 1350 wires in all-aluminum or ACSR conductors.

High tensile strength as compared to AAC conductor.

Higher conductivity as compared to ACSR conductor.

AAAC       

All Aluminium Alloy Conductors(AAAC) ASTM B 399

AREA

Stranding

Wire Dia.
 (mm)

Approx. overall diameter
 (mm)

Weight
 (kg/km)

Nominal Breaking Load
 (kN)

Nom. DC resistance at 20 Deg.
 (ohm/km)

Nominal
 AWGorMCM

Actual
 (mm2)

6

13.3

7

1.554

4.67

37

4.22

2.5199

4

21.15

7

1.961

5.89

58

6.71

1.5824

2

33.63

7

2.474

7.42

93

10.68

0.9942

1/0

53.48

7

3.119

9.36

148

16.97

0.6256

2/0

67.42

7

3.503

10.51

186

20.52

0.4959

3/0

85.03

7

3.932

11.8

234

25.86

0.3936

4/0

107.23

7

4.417

13.26

296

32.63

0.3119

250

126.66

19

2.913

14.57

349

38.93

0.2642

300

152.1

19

3.193

15.97

419

46.77

0.2199

350

177.35

19

3.447

17.24

489

52.25

0.1887

400

202.71

19

3.686

18.43

559

59.74

0.1650

450

228

19

3.909

19.55

629

67.19

0.1467

500

253.35

19

4.12

20.6

698

74.64

0.1321

550

278.6

37

3.096

21.67

768

83.80

0.1202

600

303.8

37

3.233

22.63

838

91.38

0.1102

650

329.25

37

3.366

23.56

908

97.94

0.1016

700

354.55

37

3.493

24.45

978

102.20

0.0944

750

380.2

37

3.617

25.32

1049

109.60

0.0880

800

405.15

37

3.734

26.14

1117

116.80

0.0826

900

456.16

37

3.962

27.73

1258

131.50

0.0733

1000

506.71

37

4.176

29.23

1399

146.10

0.0660

AAAC (Characteristics of A2 Conductors) IEC 61089

Code number

Area
 mm2

Number of wires

Diameter

Linear mass
 kg/km

Rated strength
 kN

D.C resistance
 Ohm/km

Wire
 mm

Cond
 mm

16

18.4

7

1.83

5.49

50.4

5.43

1.7896

25

28.8

7

2.29

6.86

78.7

8.49

1.1453

40

46

7

2.89

8.68

125.9

13.58

0.7158

63

72.5

7

3.63

10.9

198.3

21.39

0.4545

100

115

19

2.7

13.9

316.3

33.95

0.2877

125

144

19

3.1

15.5

395.4

42.44

0.2302

160

184

19

3.51

17.6

506.1

54.32

0.1798

200

230

19

3.93

19.6

632.7

67.91

0.1439

250

288

19

4.39

22

790.8

84.88

0.1151

315

363

37

3.53

24.7

998.9

106.95

0.0916

400

460

37

3.98

27.9

1268.4

135.81

0.0721

450

518

37

4.22

29.6

1426.9

152.79

0.0641

500

575

37

4.45

31.2

1585.5

169.76

0.0577

560

645

61

3.67

33

1778.4

190.14

0.0516

630

725

61

3.89

35

2000.7

213.9

0.0458

710

817

61

4.13

37.2

2254.8

241.07

0.0407

800

921

61

4.38

39.5

2540.6

271.62

0.0361

900

1036

91

3.81

41.8

2861.1

305.68

0.0321

1000

1151

91

4.01

44.1

3179

339.53

0.0289

1120

1289

91

4.25

46.7

3560.5

380.27

0.0258

1250

1439

91

4.49

49.4

3973.7

424.41

0.0231

AAAC (Characteristics of A3 Conductors) IEC 61089

Code number

Area
 mm2

Number of wires 

Diameter

Linear mass
 kg/km

Rated strength
 kN

D.C resistance
 Ohm/km

Wire
 mm

Cond
 mm

16

18.6

7

1.84

5.52

50.8

6.04

1.7896

25

29

7

2.3

6.9

79.5

9.44

1.1453

40

46.5

7

2.91

8.72

127.1

15.1

0.7158

63

73.2

7

3.65

10.9

200.2

23.06

0.4545

100

116

19

2.79

14

319.3

37.76

0.2877

125

145

19

3.12

15.6

399.2

47.2

0.2302

160

186

19

3.53

17.6

511

58.56

0.1798

200

232

19

3.95

19.7

638.7

73.2

0.1439

250

290

19

4.41

22.1

798.4

91.5

0.1151

315

366

37

3.55

24.8

1008.4

115.29

0.0916

400

465

37

4

28

1280.5

146.4

0.0721

450

523

37

4.24

29.7

1440.5

164.7

0.0641

500

581

37

4.47

31.3

1600.6

183

0.0577

560

651

61

3.69

33.2

1795.3

204.96

0.0516

630

732

61

3.91

35.2

2019.8

230.58

0.0458

710

825

61

4.15

37.3

2276.2

259.86

0.0407

800

930

61

4.4

39.6

2564.8

292.8

0.0361

900

1046

91

3.83

42.1

2888.3

329.4

0.0321

1000

1162

91

4.03

44.4

3209.3

366

0.0289

1120

1301

91

4.27

46.9

3594.4

409.92

0.0258

All Aluminlum Alloy Conductors(AAAC) BS EN 50183

Code Name

Area
 mm2

No.of wires

Diameter

Mass per unit length
 kg/km

Rated strength
 kN

DC resistance
 Ω/km

Wire
 mm

Cond.
 mm

BOX

18.8

7

1.85

5.55

51.4

5.55

1.7480

ACACLA

23.8

7

2.08

6.24

64.9

7.02

1.3828

ALMOND

30.1

7

2.34

7.02

82.2

8.88

1.0926

CEDAR

35.5

7

2.54

7.62

96.8

10.46

0.9273

DEODAR

42.2

7

2.77

8.31

115.2

12.44

0.7797

FIR

47.8

7

2.95

8.85

130.6

14.11

0.6875

HAZEL

59.9

7

3.3

9.90

163.4

17.66

0.5494

PLNE

71.6

7

3.61

10.8

195.6

21.14

0.4591

HOLLY

84.1

7

3.91

11.7

229.5

24.79

0.3913

WILLOW

89.7

7

4.04

12.1

245.0

26.47

0.3665

OAK

118.9

7

4.65

14.0

324.5

35.07

0.2767

MULBERRY

150.9

19

3.18

15.9

414.3

44.52

0.2192

ASH

180.7

19

3.48

17.4

496.1

53.31

0.1830

ELM

211

19

3.76

18.8

579.2

62.24

0.1568

POPLAR

239.4

37

2.87

20.1

659.4

70.61

0.1387

SYCAMORE

303.2

37

3.23

22.6

835.2

89.40

0.1095

UPAS

362.1

37

3.53

24.7

997.5

106.82

0.0917

YEW

479

37

4.06

28.4

1319.6

141.31

0.0693

TOTARA

498.1

37

4.14

29.0

1372.1

146.93

0.0666

RUBUS

586.9

61

3.5

31.5

1622.0

173.13

0.0567

SORBUS

659.4

61

3.71

33.4

1822.5

194.53

0.0505

ARAUCARIA

821.1

61

4.14

37.3

2269.4

242.24

0.0406

REDWOOD

996.2

61

4.56

41.0

2753.2

293.88

0.0334

All Aluminium Alloy Conductors (AAAC) BS EN 50183

Designation

Area

Stranding wire Dia.

Overall Diameter

Nominal Breaking Load

Nominal DC Resistance at 20℃

Standard Weight

mm2

No

Φ

mm

kN

Ohm/km

kg/km

ASTER 22

22

7

2

6

7.15

1.4989

60

ASTER 34.4

34.4

7

2.5

7.5

11.17

0.9593

93.8

ASTER 54.6

54.6

7

3.15

9.45

17.73

0.6042

148.9

ASTER 75.5

75.5

19

2.25

11.3

24.55

0.4388

207.4

ASTER 117

117

19

2.8

14

38.02

0.2833

321.2

ASTER 148

148.1

19

3.15

15.8

48.12

0.2239

406.5

ASTER 181.6

181.6

37

2.5

17.5

59.03

0.1831

500.3

ASTER 228

227.8

37

2.8

19.6

74.04

0.146

627.6

ASTER 288

288.3

37

3.15

22.1

93.71

0.1154

794.3

ASTER 366

366.2

37

3.55

24.9

115.36

0.0908

1008.9

ASTER 570

570.2

61

3.45

31.1

185.33

0.0585

1576

ASTER 851

850.7

91

3.45

38

276.47

0.0394

2360.7

ASTER 1144

1143.5

91

4

44

360.22

0.0293

3173.4

ASTER 1600

1595.9

127

4

52

502.72

0.021

4427.5

Aluminium Alloy Conductors (AAAC) DIN 48201

Code Number

Area.

No.of wires

Diameter

Linear Mass

Rated Tensile strengrh

DC Resistance
 at 20℃

Wire

Cond.

mm 2

mm 2

mm

mm

kg/km

daN

Ω/km

16

15.89

7

1.7

5.1

43.3

444

2.091

25

24.25

7

2.1

6.3

66.2

677

1.3703

35

34.36

7

2.5

7.5

93.8

960

0.9669

50

49.48

7

3

9

135.1

1382

0.6714

50

48.35

19

1.8

9

132.7

1350

0.6905

70

65.81

19

2.1

10.5

180.7

1838

0.5073

95

93.27

19

2.5

12.5

256

2605

0.3579

120

116.99

19

2.8

14

322

3268

0.2854

150

147.11

37

2.25

15.8

406

4109

0.2274

185

181.62

37

2.5

17.5

500.3

5073

0.1842

240

242.54

61

2.25

20.3

670.3

6774

0.1383

300

299.43

61

2.5

22.5

827

8363

0.112

400

400.14

61

2.89

26

1104

11176

0.0838

500

499.63

61

3.23

29.1

1379

13960

0.06709

625

626.2

91

2.96

32.6

1732

17490

0.054

800

802.09

91

3.35

36.9

2218

22402

0.0418

1000

999.71

91

3.74

41.1

2767

27922

0.0335

AAAC 6201- All Aluminium Alloy Conductor

AS 1531

Code Name

Strands/Wire Diameter

Overall Diameter (Approx)

Calculated Equivalent Aluminium Area

Sectional Area

Approx.
 Mass

Calculated Minimum Breaking Load

D.C.Resistence
 at 20℃

mm

mm

mm2

mm2

kg/km

kN

Ω/km

Agate

7/1.75

5.25

14.3

16.84

46

4.71

1.972

Amethyst

7/2.25

6.75

23.7

27.83

76

7.78

1.194

Diamond

7/2.50

7.50

29.3

34.36

94

9.64

0.967

Dolomite

7/2.75

8.25

35.4

41.58

114

11.6

0.799

Emerald

7/3.00

9.00

42.2

49.48

136

13.9

0.671

Garnet

7/3.75

11.3

65.8

77.28

211

21.7

0.43

Jade

7/4.50

13.5

94.8

111.3

304

31.2

0.298

Jasper

7/4.75

14.3

106

124.0

340

34.8

0.268

Opal

19/3.25

16.3

134

157.6

433

44.2

0.212

Patronite

19/3.50

17.5

155

182.80

502

51.3

0.183

Pearl

19/3.75

18.8

178

209.8

577

58.8

0.159

Ruby

37/3.00

21.0

221

261.60

720

73.5

0.128

Ruthenium

37/3.25

22.8

260

307.00

845

86.1

0.109

Rutile

19/4.75

23.8

285

336.7

925

94.4

0.09991

Sapphire

37/3.75

26.3

345

408.50

1125

115

0.0819

Spinel

61/3.25

29.3

427

506.10

1396

135

0.0662

Tantalum

61/3.50

31.5

495

586.90

1620

156

0.0572

Topaz

61/3.75

33.8

568

673.40

1858

179

0.0498

Zircon

91/4.50

49.5

1220

1447

3997

384

0.0232

6201 All Aluminum Alloy Conductor ASTM B399

Code Name

Area

Size&Stranding of ACSR with equal diameter

No. and diameter

Overall diameter

Weight

Nominal breaking load

Nominal

Actual

MCM

mm2

AWG or MCM

mm

mm

kg/km

kN

AKRON

30.58

15.48

6

7/1.68

5.04

42.7

4.92

ALTON

48.69

24.71

4

7/2.12

6.35

68

7.84

AMES

77.47

39.22

2

7/2.67

8.02

108

12.45

AZUSA

123.3

62.38

1/0

7/3.37

10.11

172

18.97

ANAHEIM

155.4

78.65

2/0

7/3.78

11.35

217

23.93

AMHERST

195.7

99.22

3/0

7/4.25

12.75

273

30.18

ALLIANCE

246.9

125.1

4/0

7/4.77

14.31

345

38.05

BUTTE

312.8

158.6

266.8

19/3.26

16.3

437

48.76

CANTON

394.5

199.9

336.4

19/3.66

18.3

551

58.91

CAIRO

465.4

235.8

397.5

19/3.98

19.88

650

69.48

DARIEN

559.5

283.5

477

19/4.36

21.79

781

83.52

ELGIN

652.4

330.6

556.5

19/4.71

23.54

911

97.42

FLINT

740.8

375.3

636

37/3.59

25.16

1035

108.21

GREELEY

927.2

469.8

795

37/4.02

28.14

1295

135.47